Rated Current: 500A and 630A

Number Of Poles: Available in 3P and 4P configurations

Rated Working Voltage: 400V/415V

Our high-quality electrical components are manufactured in China, making us one of the leading suppliers in the industry. Our factory specializes in producing reliable circuit breakers that meet various industrial standards, ensuring safety and efficiency in your operations. Choose us for dependable products that cater to your electrical needs.

Request a Quote

PRODUCTS DETAILS

The operating interface of the ARM6HUE knob controller after being powered on is shown in the following figure.

ARM6HUE Knob Controller Interface
Key Description Indication
  • 1. Normal operation indicator light
  • 2. Pre alarm indicator light
  • 3. Overload fault indication
  • 4. Communication instructions
Switch & Interface
  • 5. Code dialing/remote control switching
  • 6. Neutral pole protection ratio
  • 7. Test interface
  • 8. Lock catch
Button Description Adjustment Panel
  • 9. Long delay current setting IR
  • 10. Long delay tripping delay tR
  • 11. Short delay tripping Isd
  • 12. Short delay tripping delay tsd
  • 13. Short circuit instantaneous Ii
  • 14. Ground fault tripping Ig
  • 15. Ground fault tripping delay tg
Indicator Lights Definition & Status Reference
Normal Status Green light: flashing indicates normal operation, while not on or constantly on indicates abnormal operation.
Long Delay Fault Yellow light off, red light flashing: Long delay fault.
Overload Warning Yellow light flashing and red light off: Overload warning (slow flashing greater than 90% of the long delay setting value, fast flashing greater than the long delay setting value).
Short Delay Fault Yellow light on, red light flashing: Short delay fault.
Ground Fault Yellow light on, Red light on: Ground fault.
Instantaneous Fault Flashing yellow light and flashing red light: Instantaneous fault.
Communication Communication indication: If there is a cabinet door unit, regardless of whether there is an upper computer, it indicates communication with the cabinet door unit. If there is no cabinet door unit, but there is an upper computer, it indicates communication with the upper computer.
ARW1
Frequently Asked Questions (FAQ)
What does it mean if the green operation light is constantly on or off?
Under normal operation, the green light should continuously flash. If the green light is completely off or constantly on without flashing, it signifies that the ARM6HUE controller is experiencing abnormal operation.
How can I identify an overload condition before a trip occurs?
An impending overload is signaled by a flashing yellow light while the red light remains off. A slow flash indicates the current has exceeded 90% of the long delay setting value, while a fast flash indicates the current has exceeded the full setting value.
What does it indicate when both the yellow and red indicator lights are steady on?
When both the yellow and red lights remain continuously on, it indicates a ground fault tripping event within the protection circuit.
What causes both the yellow and red lights to flash simultaneously?
Simultaneous flashing of both the yellow and red indicators signifies an instantaneous short-circuit fault condition.
How does the ARM6HUE manage communication priority between devices?
If a cabinet door unit is connected, the controller prioritizes and indicates communication with the door unit regardless of upper computer presence. If no door unit is present, it directly indicates communication with the upper computer.
What parameters can be adjusted directly from the front panel knobs?
The panel allows precise configuration of long delay current (IR), long delay trip timing (tR), short delay tripping threshold (Isd), short delay delay (tsd), instantaneous tripping (Ii), ground fault current (Ig), and ground fault delay (tg).